COMPARTMENTING AND FIRE PROOFING SEALINGS

PL 011 - PLASTERBOARD WALL

CROSSING OF METAL PIPE

SPECIFICATION

 

  • KM-FF108 graphitic intumescent material

  • KM BOARD V1 mineral fibre panel, 150kg/cm density with fire resistant coating on one side

  • KM SEALER F silicone monocomponent putty

 

FITTING UP

 

Cut KM-FF108 and set up it to seal the blank between pipe and wall.

Shape the panel KM BOARD V1 and seal the blank between duct and wall; two panels must be fit up back to back with the treated side outwards. Seal panel with KM SEALER F putty.

Sealed with fire resistant putty KM SELAR F on both sides of the wall

 

CERTIFICATION

 

  • LAPI 4, pos. 8.