top of page

COMPARTMENTING AND FIRE PROOFING SEALINGS

FIRE FIGHTING GRAPHITIC

GASKET SYSTEM FOR CROSSING HOLES AND BUILDING JOINTS

KM-FF 108

GENERALITY

 

The system is made up of a graphitic fire resistant intumescent material, to seal small crossing holes of a cable bundle. Suitable for cracks and to seal gaps of 30 mm between air-conditioned tubes and/or steel pipes and the crossed walls; to seal building joints and cracks between walls and concrete slabs compartment.

 

DESCRIPTION

 

Fire fighting graphitic sponge KM-FF108.

Silicone fire-resistant putty KM SEALER F.

 

SIZE

1000x50mm, thickness of 30 mm.

 

FUNCTIONALITY

 

Crossing of a cable bundle through a small circular hole. Roll the sponge KM-FF108 around the cables bundle until the hole is filled and seal both sides of the hole with fire-fighting putty KM SEALER F.

Crossing of an air conditioned duct or metal pipe, with free small space to be sealed (< 30 mm). Insert the sponge KM-FF108 and fill the free space between wall and plant, seal with fire-fighting putty KM SEALER F.

Sealing of a building joint and/or a crack between wall and concrete slab. Insert the sponge KM-FF108 and fill the gap. Seal with fire-fighting putty KM SEALER F.

 

CERTIFICATIONS

 

  · According to European Standard UNI-EN 1366-3, EI 180 on masonry walls.

  · According to European Standard UNI-EN 1366-3 EI 120 on plasterboard walls.

 

 

TECHNICAL DATA

Colour:                                            dark grey

Density:                                           225 kg/m3

Free expansion:                              2 times at 450°C in 15 min

Pressure:                                         5 bar at 400 °C

Flashpoint:                                      non-flammable

Reaction temperature:                  250°C

Compressibility:                              up to 50%

Dangerous reactions:                     none observed

Storage:                                           inside room not exposed to water and moisture

Transport:                                       no restrictions on land

                                                         no restrictions ICAO/IATA-DGR

                                                         (not in direct contact with edible products)

 

 

FURTHER INFORMATION

It does not require any precautionary measures for its use and handling

 

Acute effects to exposure:            none

Classification and labelling:          the material does not require any special labelling

Warnings:                                        none

Safety advice:                                 none