COMPARTMENTING AND FIRE PROOFING SEALINGS
FIRE FIGHTING COLLAR
FOR COMBUSTIBLE PIPE
KM-FSG

GENERALITY
The collar KM-FSG is made up of a galvanized sheet metal U-shaped shell, containing strips of graphitic intumescent material with high thermal expansion KM-FF107.
DESCRIPTION
Fire fighting collar KM-FSG, for combustible ell pipes (90°/45°) from Ø 75 mm to Ø 140 mm
FUNCTIONALITY
Combustible ell pipes (90°/45°) are protected by the collar KM-FSG. They are utilized to protect pipes, through structures of compartmenting if impossible to set up a normal collar KM-FS.
FEATURES
The semicircular cap of collar KM-FSG must be set up to the combustible ell pipe with metal stud bolts. The open legs must stick to the combustible pipe and fix to the structure of the compartmenting.
The collar is fixed to the lower side of the slab (ceiling side).
CERTIFICATIONS
-
According to the European Standard UNI EN 1366-3, EI180
TECHNICAL DATA
Shell: galvanized steel
Content: graphitic based intumescent strips KM-FF107
Density: 630 kg/m³
Free Expansion: at 400 °C in 15 min
Pressure: 14 bar at 400°C
Flashpoint: unflammable
Reaction temperature: 250°C
Dangerous Reaction : none observed
Storage: in a closed environment not exposed to water and moisture
Transport: no restriction on land
No restrictions ICAO/IATA-DGR
(not in direct contact with edible products)
FURTHER INFORMATION
No care is required
Acute effects to exposure: none
Classification and labelling: none required
Warning: none
Safety advice: none